Description:
This listing includes: 1 unit of controller for pressurized solar water heating system, 110V.
It can connect 2000w(Max.) electrical element heater @ 110V.
Application:
It can be used for the solar hot water heating system: 1 collector array – 1 storage tank – 1 pump and auxiliary heating.

Delivery list
(remark:there’s no power cable in the package, please prepare a power cable of 2.5mm2)
Function Introduction:
The solar circuit pump (R1) is switched on as soon as the switch-on temperature difference (△T on) between the collector array (T1) and the storage tank (T2) is reached.
If the temperature difference between the collector array (T1) and storage tank (T2) drops below the switch-off temperature difference (△T off), , or the temperature of storage tank (T3) reaches the preset maximum storage temperature, then the solar circuit pump (R1) is switched off.
Back-up heating by auxiliary boiler: within the preset time section of back-up heating, if the temperature T3 is below the switch-on temperature, then the circulation pump ( H1) of back-up heating is triggered, when T3 is heated to the switch-off temperature, circulation pump H1 of back-up heating is ceased.
APPLICATIONS CAPACITY
Max.number of collectors:1
Max.number of storage tanks:1
Max.number of relays:4
Max.number of sensors:5
Max.number of visualization application system: 1
Size of Keypad:120mm x 120mm x 18mm
Size of Controller(1.5KW version): 200mm x140mm x43mm
Power supply: AC220-240V, 50-60Hz
Power consumption: < 2.5W
Rated impulse voltage: 2.5KV
Housing: Plastic ABS
Protection type: IP41
Mounting: Wall mounting
Operation: 10 push buttons at the front cover.
Accuracy of temperature measuring: ± 0.1℃
Range of collector temperature measuring: -10℃ ~220℃
Range of tank temperature measuring: 0℃ ~110℃
Suitable power of pump: 3 pumps possible to be connected
Suitable power of HK (backup electrical heater): 1pc : ˂=2000KW (@110V)
Inputs: 3 sensors
1pcs*Pt1000 sensor (≤500℃) for collector (silicon cable≤280oC)
2pcs*NTC10K B3950 sensor (≤ 135℃) for tank (PVC cable ≤105oC)
Outputs: 4 relays for circulation pump and backup heating
3*Electronmagnetic relay Max.current: 2A
HK relay(4KW version):20A
Ambient temperature: -10℃ ~ 50℃
Water proof grade: IP41
MAIN FUNCTION:
DATE---Date setting
Timed heat---backup heating
Circle---Hot water circulation
LOAD---Setup Loading tank1
COL---Collector1
PUMP---Pump control mode
COOL---Cooling function
AUX---Auxiliary function
MAN---Manual mode
BLPR---Blocking protection function
OTDI---Thermal disinfection function
FS---Flow meter type selection.
UNIT---C-F unit switch
RST---factory setting
PASS--- password set
Holiday function
Screen Protection
Trouble Protection
Trouble Checking